FIRE DETECTION SYSTEM
FIRE ALARM CONTROL PANEL
- UL LISTED & FM APPROVED
- Multi-loop (2-4) analog-addressable
- Per loop support 126-127 sensor and maximum cable length 3000 M
- Configurable through keypad
- Programmable Inputs – 3, Programmable relays – 5
- Supervised Powered Outputs – 3
- Programmable Function button on front display
- Fire Drill button on front display
- Day and night sensitivity settings
- Power Supply: 5.25 Amp, regulated & integrated
- Battery size: Up to 17 Ah in standard enclosure
- Access levels: 3, Access key switch: Yes
- Recognized for use in High Rise
PHOTOELECTRIC SMOKE SENSOR
- UL Listed & FM Approved
- Operating Voltage: 17-41 VDC
- Standby Current: 450μA
- Alarm Current: 540μA
- UL Temperature Range: 32º F to 115º F
- Operating Temperature Range: 14º F to 122º F
MULTI SENSOR SMOKE AND HEAT
- UL Listed & FM Approved
- Operating Voltage: 17-41 VDC
- Standby Current: 450μA
- Alarm Current: 540μA
- UL Temperature Range: 135º F to 150º F
- Operating Temperature Range: 14º F to 122º F
BEAM DETECTOR
- Rated Voltage 24VDC
- Supply Voltage 19VDC – 33VDC
- Supervisory Current Emitter 50μA @ 24VDC Receiver 200μA @24VDC
- Alarm Current 20mA @ 24DC
- Operating Temperature Range 14° F – 122° F
- Allowable misalignment Emitter +/- 0.5° angle (MAX) Receiver +/-1.0°
ADDRESSABLE PULL STATION
- UL Listed & FM Approved
- Single or Dual Action
- Rated voltage : 17-41 VDC
- Average consumption: 3.5mA
- Alarm current: 17-28 VDC
- UL ambient installation temperature range: 32°F to 100°F
- Operating temperature range: 14°F to 122°F
HORN/ STROBE
- UL Listed & FM Approved
- Nominal voltage 24VDC
- Switch selection for high or low dBA
- Switch for chime, whoop, mechanical and 2400Hz tone
- Tamperproof re-entrant grill
- Switch for continuous or temporal 3
- Silence horn while strobes flashing
- Wide voltage range 16-33VDC or FWR
SHORT CIRCUIT ISOLATOR
- UL Listed & FM Approved
- Absolute Max. Voltage: 41 VDC
- Supply Voltage Nominal: 33VDC
- Normal Current : 270μA
- Active Current Consumption (Short Circuit Condition): 10mA
- UL Ambient Installation Temperature Range: 32º F to 120º F
- Visual Indicator (Yellow Status LED)
SUPERVISED RELAY MODULES
- UL Listed & FM Approved
- Supply Voltage Nominal: 25.3-39VDC
- Auxiliary Supply Voltage: 24 VDC
- Current Consumption on Auxiliary Power Lines: 50μA (Typical)
- Maximum Quantity per Loop: 127
- Ambient Temperature Range: 32º F to 120º F